10.5kv 3000kw Dry Type Load Bank for Generator Testing
Basic Info.
Model NO. | 10.5KV 3000kW Load bank |
Rated Load | >1000kg |
Application | Generator Test |
Customized | Customized |
Surface Treatment | Powder Coating |
Protection Grade | IP55 |
Fan Working Voltage | AC380V/50Hz/60Hz, 3 Phases 4 Wire |
Weight | 6000kg |
Rated Power | 3000kw |
Insulation Grade | F Class |
Frequency | 50Hz |
Transport Package | Containerised |
Specification | 6058*2438*2591 |
Trademark | Triumph Load |
Origin | Hebei, China |
HS Code | 9030339000 |
Production Capacity | 1000PCS/Year |
Product Description
10.5kv 3000kw Dry Type Load bank for Generator Testing
1. Product Introduction
10.5kV 3000kW Dry Type Loadbank for Generator Testing
High voltage load bank,the optional voltage range is 6.6KV~35KV,can be directly used for large high voltage generator,
need not to be equipped with conventional step-down transformer.We can also provide regular load bank for high voltage
equipment,need to use step-down transformer together.
2. 10.5kV 3000kW Dry Type Loadbank for Generator Testing Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment
3. 10.5kV 3000kW Dry Type Loadbank for Generator Testing Working Environment
Altitute:≤2500m
Temperature:-10°C~50°C
Humidity:≤95%RH
Working Mode:Continuous work(>6hours continuous long-term work per day)
4. 10.5kV 3000kW Dry Type Loadbank for Generator Testing Technical Specifications
System Parameters (Single set) | |
Rated Voltage/ Frequency | AC10.5KV/50Hz, 3 phases 3 wire |
Installer Capacity | 3000kW |
Step Load | 50KW,100KW,200KW,400KW,800KW,1500KW,6 steps |
Power Factor (PF) | 1 |
Load Tolerance | 5% |
Display Precision | 0.5 grade |
Control Power Supply | AC380V/50Hz/60Hz, 3 phases 4 wire |
Insulation | F |
Max Protection Grade | IP55 |
Working Mode | Continuous |
Cooling | Forced air cooling, Horizontal inlet air, Vertical cooling |
Casing Structure | Standard 20 feet container, with a ladder to top |
Transportation | Hoisting, there are lifting lugs in top of casing |
Dimension | 6058mm×2438 mm×2896mm |
Weight | About 6000kg |
Working Environment Parameters | |
Ambient Temperature | -20ºC~+55ºC |
Relative Humidity | ≤95% |
Altitude | ≤2500 meters |
Atmospheric Pressure | 86~106kPa |
Working Temperature | Temperature inside container: less than 35ºC,forced-air cooling |
5. 10.5kV 3000kW Dry Type Loadbank for Generator Testing Overall Appearance
5. Why choosing usThe earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.The most patent technology and scientific research awards gainer in China.Advanced detection method and strict inspection procedure build the qualified quality.Customized production meet the individual requirement.Prompt delivery & excellent after sales service.Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.6. Contact Information