3kw, 3.5kw, 4kw, 5kw, 6kw, 7kw, 10.5kw, 12kw AC/DC Dummy Load Bank for Sale
Product Description3kW,3.5kW,4kW,5kW,6kW,7kW,10.5kW,12kW AC/DC dummy load bank > Application IST commissioning in data c
Basic Info.
Model NO. | RT3-12KWLB |
Application | Data Center/UPS |
Customized | Customized |
Surface Treatment | Powder Coating |
Transport Package | Carton + Wrapping Film |
Specification | 3U-12U |
Trademark | Rata |
Origin | China |
HS Code | 9030899090 |
Production Capacity | 100 Sets/Month |
Product Description
Product Description3kW,3.5kW,4kW,5kW,6kW,7kW,10.5kW,12kW AC/DC dummy load bank> Application
IST commissioning in data center & data room. Testing both electrical network (UPS, Diesel generator, etc.) & air conditioning (free cooling, etc.), the rack-mounted load bank is simulating exact electrical & air conditioning impact of servers in the rack cabinet.
> Parameter(3kW for reference)
Product name | 220V AC 3KW Rack Mounted Load Bank | |||
Model No. | RT3KWACLB | |||
Capacity | 3kW resistive load | |||
Nominal voltage | 220V AC | |||
Min. step | 500W/1000W | |||
Load steps | > 500W,500W,1000W,1000W> 1000W,1000W,1000W | |||
Load adjust | MCB(ABB/Schneider brand) for step control | |||
Power source input | Single | |||
Fan working source | Internal | |||
Protection | IP23 | |||
Duty cycle | Continuous | |||
Operation Temp. | 0 to 40 ºC | |||
Storage Temp. | 0 to 60 ºC | |||
Cooling | 2 low noises,horizontal force air cooling DC fans, Installed inside the load bank, powered from the test source. Each fan 186CFM,total 372CFM. | |||
Air flow | Air is sucked in the front and blown out horizontally at the rear. | |||
Technology | Expanded metal grids type insulated by ceramic rings | |||
Packing | Carton+wrapping film | |||
Dimension (L*W*H) | 3U(490*352*130mm) | |||
Weight | 12kg | |||
Movement | 2 steel handles at panel side | |||
Element type | High temperature 8020 Ni-chrome finned resistor | |||
Power connection | Power connected at the rear side as following picture shows | |||
Function options | > High temperature> Air volume adjust> CFM display | |||
Power cable | > C13/C19/C20> 1.5~2m> 32A water proof 3 in 1 plug: the plug with blue color connected to the external power source,and another three plug with black color connected to the load bank. |