5500kVA Resistive Inductive Load Bank for Generator Testing
HomeHome > Products > Load Bank > 5500kVA Resistive Inductive Load Bank for Generator Testing
5500kVA Resistive Inductive Load Bank for Generator Testing

5500kVA Resistive Inductive Load Bank for Generator Testing

5500KVA Resistive Inductive Load Bank offers a 0.80 power factor load and is designed for testing large generators, swit
Basic Info.
Model NO. AC400-5500kVA-RL
Use Place Outdoor
Reactive Load 3300kvar
Cooling Forced Air Cooling
Power Factor 0.8
Resistive Load 4400kw
Rated Voltage 400VAC, 3 Phase, 50Hz
Transport Package Container
Specification ISO9001: 2008
Trademark Triumph load
Origin Hebei, China
HS Code 90303390
Production Capacity 3 Units/Month
Product Description

5500KVA Resistive Inductive Load Bank offers a 0.80 power factor load and is designed for testing large generators, switchgear, transformers and UPS systems. The structural skid with fork lift pockets allows for portability and is ideal for shipyards, power plants, OEMs and data centers. It is perfect solution for regularly scheduled maintenance testing and commissioning of mission-critical standby emergency power systems where rated kVA, rated power factor and rated current testing is required.
Application
Large generator system testing in ocean engineering, drilling facilities,ship construction etc field
Factory testing for generator, static voltage characteristic test, speed characteristic test;
Marine generator overload protection test,parallel operation test,reverse power and reverse current protection test
Assist shipyard in mooring test,sea trial test
Assist with the acceptance of the vessel generator test
Eliminate the carbon deposition of generator
As the generator loading system
Periodic running test for standby generator
UPS inspection and maintenance
Ship battery charging/discharging system testing
The acceptance of new system and testing of servicing equipment

Technical Parameters

5500kVA Resistive Inductive Load Bank for Generator Testing

Rating voltage/frequency

400VAC 3 phase 4 wire, 50Hz, phase voltage 230VAC

Max Load Power

Apparent Power: 5500kVA

Resistive Load: 4400kW; Inductive Load: 3300kvar

Load Resolution

Resistive Load: 30 steps, 1,2,2,5,10,10,20,50,100,21*200kW

Inductive Load: 25 steps, 1,2,2,5,10,10,20,50,100,100,15*200kvar

Power Factor

0.8

Load Tolerance (each step)

±5%

Load Tolerance(overall)

±3%

Fan Control Power

380VAC 3 phase 4 wire, 50Hz, phase voltage 220VAC

Wire Connection

Load bank input--Copper bar (star coupling "Y")

Control power input--Connector-bar

Communication Interface

RS485,RS232

Insulation

F

Max Protection Grade

IP55

Way of Working

Continuous Working

Cooling

Forced air cooling, horizontal inlet air, vertical exhaust cooling

Enclosure

Container type with a ladder, air inlet and outlet with mesh enclosure and protection door

Transportation

Hoisting

Color

RAL7035

Dimensions

About 6058mm*2350mm*2591mm(L×W×H)

Weight

About 25000kg

Operating Environment Parameter

Ambient Temperature

-10ºC~+50ºC

Relative Humidity

≤95%

Atmospheric Pressure

86~106kPa

Brands of Main Components

Contactor

CHINT

Fuse

DELIXI

MCU

INFINEON

Alloy Resistor

(self-developing)

Data Processing Software

(self-developing)


Structure ChartApplication CaseWorkshop