Dual Voltage Load Bank Rack Mounted Loadbank for Data Center
HomeHome > Products > Rack Mounted Load Bank > Dual Voltage Load Bank Rack Mounted Loadbank for Data Center
Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center This unit specially designed for data center, it's safe, re
Basic Info.
Model NO. AC/DC 220/270V-4KW
Transport Package Wooden Box
Trademark TriumphLoad
Origin China
HS Code 9030339000
Production Capacity 20000 Sets/ Per Year
Product Description

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

This unit specially designed for data center, it's safe, reliable, small volume and can simulate the on-site server load. Heating element designed by special alloy resistance. In the medium and small power heating occasions, the alloy resistance element has the advantages of small temperature drift, long service life and high precision.

1. Rack Mounted Load Bank 4KW Technical Parameters

System Parameter

Rating voltage/frequency

Single phase 220VAC/50Hz

Max Load Power

Resisitive Power: 4kW

Load Resolution

Resistive Load: 4 steps. 1kW; 1kW; 1kW; 1kW.

Power Factor

1

Load Tolerance

±5%

Insulation Grade

Grade F

Way of Working

Continuous Working

Cooling

Forced air cooling, intake air in front and exhaust cooling in back

Case Color

Black

Case Dimension

About431mm*451mm*177.8mm(L*W*H)

Weight

About 15kgs

Working Environment Parameter

Ambient Temperature

-10ºC~+40ºC

Relative Humidity

≤95%

Altitude

≤1500 meters

Atmospheric Pressure

86~106kPa

Brands of Main Components

Gear Switch

ABB

2. Rack Mounted Load Bank 4KW Main Functions

(1) Load Test: User can load any power within rated power, and test the output capacity of under test power supply.

(2) Control Mode: The laod bank is with 1 gear switch and 1 fan switch, can control loading/unloading after starting the fan.

(3) Fan Power Supply: Fan is installed near the air outlet, and powered on A/N phase. At first, connecting to power supply, turn on the fan switch, the fan can be started, then can load/unload through the gear switch. Don't to load before fan started.

(4) Temperature Protection: There will be sound and light alarm when the load bank temperature exceeds the safety threshold value.

(5) Load bank Cable: The internal cable adopts multi core flame retardant flexible cord, and with glass fiber casing protection

3. Rack Mounted Load Bank 4KW Operation Caution

The load bank is with 1 gear switch and 1 fan switch. At first, turn on the fan switch to start up, then can load/unload through the gear switch after the fan work normally, Max power is 3.6kW. Please keep the fan switch is in the open state when operating. If overheat alarm, please turn off the power switch and then check the equipment problem.

4. Rack Mounted Load Bank 6KW Picture

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center


Our company

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

Dual Voltage Load Bank Rack Mounted Loadbank for Data Center

6. Why choosing us

  1. The earliest and most professional manufacturer of AC/DC Load Bank in China, dedicated to this industry for more than 20 years.
  2. The most patent technology and scientific research awards gainer in China.
  3. Advanced detection method and strict inspection procedure build the qualified quality.
  4. Customized production meet the individual requirement.
  5. Prompt delivery & excellent after sales service.
  6. Cooperate with many well-known enterprise, offer OEM and ODM service to world famous brands.
  7. Certified with China Classification Society (CCS) and ISO9001:2008 Quality Certificate.
  8. Triumph Load is the first brand in the emergency power supply test & maintenance industry in China.