500kw AC Dummy Resistive Dry Type Load Bank
Dry Type Load Bank Overview Rata resistive load bank is a special equipment for generator type test and delivery inspect
Basic Info.
Application | Generator/Genset/UPS |
Customized | Customized Available |
Surface Treatment | Paint |
Name | Dry Type Load Bank |
Transport Package | Film Wrapping/Wooden Box |
Specification | Reference the specification following |
Trademark | Rata |
Origin | China |
HS Code | 9030899090 |
Product Description
Dry Type Load Bank
Overview
Rata resistive load bank is a special equipment for generator type test and delivery inspection.The optional intelligent test system can automatically complete the measurement of all electrical parameters of the generator and automatically generate various charts,curves and reports. Our high-voltage load can directly measure the high-voltage power supply without transformer.They generally adopt remote operation mode,which is connected with the load body through the network cable of notebook or experimental platform to control the load and ensure the safety of operators. Load Bank Application1. Generator set: diesel generator set factory test2. Data center: load test of back mounted generator set3. Offshore ships: marine generator unit test, oil platform load test4. Ships: ship generator set test5. Emergency power supply: regular test of AC and DC emergency power supply6. Power plant: load simulation loading, transformer on load test Load Bank Electrical DataNominal voltage: AC400V/630V/10.5kv/CustomizedNominal power: 100kW to 8000kW or CustomizedFrequency: 50/60HzPower factor: 1.0Min. step: 1kWLoad step: according to customer needsLoad connection: copper bar,3-phases 4 wiresResistor: Each resistance element: insulation impedance DC2000V/10MΩ above Withstand voltage AC2000v for 1 min; Resistance error of each resistance tube: ±2%Can stable work under 350ºC.Load control: local manual button control,remote PC/console control Loading accuracy: ≤ 3% Three phase balance: unbalance degree: ≤3%Working mode(Duty cycle): continuous work / customizedLoad protection: short circuit,overcurrent,high temperature,fan fault protectionPour source: AC380V/50HzCooling mode: forced air cooling,horizontal air outlet,vertical air outletInsulation class: FMeasurement accuracy: the display accuracy is 0.5,the sampling accuracy is 0.2Electrical parameter display: three phase voltage,three-phase current,frequency, power,etcVoltage rising mode: realized by transformerLoad expansion: parallel expansion of multiple load containersStandard: meet international standard,ship standard and telecommunication standardTransport: load-bearing lifting hole,castors or forklift hole can be selected.Color: blue / customizedAmbient temperature: -20ºC to 50ºCHumidity: up to 100%Altitude: up to 2500mAtmospheric pressure: 86 to 106kPaDimension: reference above tableWeight: reference above tableCustomized Accepted | ||||
Power(kW) | Voltage(kV) | Frequency(Hz) | Size(mm,L*W*H) | Weight(Kg) |
Low voltage | ||||
100 | 0.4 | 50 | 1100*900*1000 | 320 |
200 | 0.4 | 50 | 1350*1100*1100 | 450 |
300 | 0.4 | 50 | 1500*1200*1200 | 650 |
400 | 0.4 | 50 | 1700*1500*1500 | 830 |
500 | 0.4 | 50 | 1700*1600*1600 | 950 |
600 | 0.4 | 50 | 1800*1600*1600 | 1150 |
800 | 0.4 | 50 | 1900*1800*1700 | 1900 |
1000 | 0.4 | 50 | 2300*1700*2100 | 2100 |
1200 | 0.4 | 50 | 2500*1800*2200 | 2300 |
1500 | 0.4 | 50 | 2500*1860*2300 | 2600 |
1800 | 0.4 | 50 | 3000*2000*2300 | 4000 |
2000 | 0.4 | 50 | 3000*2000*2300 | 5000 |
2500 | 0.4 | 50 | 4000*2438*2500 | 6000 |
3000 | 0.4 | 50 | 6000*2438*2500 | 7000 |
Medium voltage | ||||
1000 | 6/10.5 | 50/60 | 3000*2438*2500 | 3500 |
1200 | 6/10.5 | 50/60 | 4000*2438*2500 | 3900 |
1500 | 6/10.5 | 50/60 | 4000*2438*2500 | 4500 |
1600 | 6/10.5 | 50/60 | 5000*2438*2500 | 5000 |
1800 | 6/10.5 | 50/60 | 5000*2438*2500 | 6500 |
2000 | 6/10.5 | 50/60 | 6000*2438*2500 | 7500 |
2200 | 6/10.5 | 50/60 | 6000*2438*2500 | 8000 |
2500 | 6/10.5 | 50/60 | 6000*2438*2500 | 10000 |
3000 | 6/10.5 | 50/60 | 7000*2438*2500 | 12000 |
4000 | 6/10.5 | 50/60 | 8000*2438*2500 | 14000 |
5000 | 6/10.5 | 50/60 | 9000*2438*2500 | 15000 |
6000 | 6/10.5 | 50/60 | 12000*2438*2500 | 16000 |
7000 | 6/10.5 | 50/60 | 12000*2438*2500 | 17000 |
8000 | 6/10.5 | 50/60 | 12000*2438*2500 | 18000 |
Product Pictures
Company ProfileRata technology was established in 2013 and located at Luojiang High and New Technology Zone, Deyang City, China. The factory is nearby the high way and national road, with convenient shipment. It is about 5 hours from our factory to the nearest port. There are professional technicians and skilled workers. During past 9 years, we are focus on development and production of kinds of load bank. By far, we have obtained 15 patents of load bank, ISO 9001 certificates and 8 computer software copyrights. We are not only focus on products quality, but also on service. By far we obtained 5 stars contract performance capacity certificate and 7 stars after sales service certificate. Rata Technology mainly produce and sale resistive load bank, resistive inductive combined load bank, resistive inductive and capacitive combined load bank, rack mounted load bank, DC load bank, electrical load bank and battery discharger. Battery discharge test: Power battery, lead acid battery and fuel battery, BMS and battery protection equipment test, test of communication power supply and server power supply. Virtual load test of solar array and industrial motor. Test of DC charging pile, charging module and other electronic power devices. Our load bank have been exported to Europe, Africa, , Asia and other regions and have good reputation. You are welcome to visit our factory and look forward to cooperate with you.